Tenzan Wyspa

Polski

Wyspa: plan power during a long blackout

Demo: an invented town and real 2024 weather. Simulation only, not connected to any equipment.

Solar panels, a battery and a diesel generator cannot power every facility, so Wyspa proposes, hour by hour, which to switch off and says why.

Time

Battery at hour end
Diesel at hour end
Solar
Off now
Next

Power map
PartValue

Result

Three ways to run the same power system

MeasureNo plan (everything on)Only priority 1Wyspa plan
Priority 2, share of needed energy
Priority 3, share of needed energy

No plan: nothing is switched off, so in any hour the facilities need more than the system can give, the whole system shuts down, like a blown fuse. Only priority 1: priorities 2 and 3 stay off the whole time. Wyspa plan: the method under How the plan decides. All three run on the same diesel: the tank minus the diesel kept back.

Hour by hour

Show on map and chart

Power served by priority, solar output, battery charge, diesel generator output and the state of each facility for every hour.

Hour-by-hour table

Facilities

What happens and why

Your decision

Who loses power in the Wyspa plan

How much diesel is needed?

How the plan decides

  1. Each hour, the planner goes down the list of facilities: priority 1 first, then in list order inside a priority. A facility runs only if every facility already on still keeps power to the end of the outage in the planner's forecast. If not, it is switched off, and the planner still tries the smaller ones below it.
  2. The forecast is the recorded weather of those days with less sun, as set under Equipment. The plan also knows when the outage ends. The current hour uses the recorded solar output.
  3. Power flows in a fixed order: solar first, then the battery, then the diesel generator. Spare solar charges the battery. The generator starts only when the battery cannot cover the hour, runs at least at its minimum output, and its diesel use follows the HOMER fuel curve.
  4. The plan keeps no diesel or battery charge for after the outage, unless you keep diesel back under Equipment.
  5. The planner only proposes and explains. A person checks who loses power and decides.

Words used here

Local power system (microgrid)
Solar panels, a battery and a generator that power a few facilities without the main grid.
Wyspa
Polish for "island". A power system cut off from the main grid runs as an island.
kW and kWh
kW is power at one moment. kWh is energy over time: 1 kW for 1 hour is 1 kWh.
Modelled hour
Each step is one hour. Power values are the hour's average; battery and diesel show what is left at the end of the hour. Hours with power are totals, not one unbroken stretch.
Assumed battery minimum
Charge the model never takes from the battery. Assumed minimum: 10% in this demo.
No plan (everything on)
Nothing is switched off. If the facilities need more power than the system can give, the whole system shuts down for that hour, like a blown fuse.

Briefing: Wyspa plan (demo)

Demo: an invented town and real 2024 weather. Simulation only, not connected to any equipment.

Simulation only. Not connected to equipment. Do not use as a switching instruction.

Reviewed by (name, signature): ____________________